AURA-AK

AURA-AK

Compact Digital Fault Recorder (DFR)

  • current circuits connected without intermediate terminals
  • 32 analog and 64 binary channels
  • integrated single-unit design
  • cost-effective

The AURA-AK recorder can contain up to eight replaceable modules, each with four analog and eight binary measurement channels. Modules are available with either current or voltage measurement channels. Current is measured by passing the current-circuit conductor through a ferrite aperture, without adding resistance to the circuit. Voltage and binary circuits connect directly to the module terminals.

Request a quote

The AURA-AK digital fault recorder is an integrated unit with measuring transducers and binary signal monitoring circuits combined in replaceable modules. It can contain up to eight modules, each with four analog and eight binary measurement channels. Current-input or voltage-input modules are fitted to the customer’s specification.

Current circuits are connected using ferrite rings with an 8 mm internal diameter. Passing the current-circuit conductor through the ferrite ring forms the measuring circuit without adding resistance to the current circuit. Voltage and binary circuits connect directly to the unit terminal blocks, without intermediate terminals.

Example of AURA-AK circuit wiring

Design

The central unit housing is made from an aluminum extrusion, providing electromagnetic shielding and the mechanical strength required for long-term industrial operation. Plug-in connections allow functional modules to be replaced quickly when necessary.

Applications

The compact recorder measures and monitors normal and fault conditions in power-sector and industrial equipment. It is a cost-effective choice for applications with a relatively small number of monitored channels.

AURA-AK can operate independently as a digital fault recorder or as part of a distributed automated measurement system.

Measuring instrument type approval certificate
Russian State Register number: 72492-18

AURA-AK comprises an industrial PC-based central unit, system software, measuring transducers and communication equipment.

AURA-AK variants offer different combinations of current and voltage transducers.

Application software for PC workstations running Windows is included.

The AURA-AK main unit has a vibration-resistant aluminum-profile enclosure for industrial service and contains a fanless single-board computer.

The front panel contains:
  • LED indicators;
  • buttons for switching the recorder on and off, triggering a test recording and resetting alarms;
  • binary signal connector;
  • analog transducer modules with two-pin voltage-circuit connectors and transformers with apertures for current-circuit conductors;
  • connector for the 12 V DC supply cable;
  • terminal block for external alarm circuits;
  • the processor board connection panel for external devices.

Windows XP Embedded or Linux operating system.

AURA-AK main unit

An AURA-AK transducer module is a replaceable unit containing measuring transducers and binary signal monitoring circuits. The AURA-AK recorder supports up to eight of these modules, each with 4 analog and 8 binary measurement channels. Modules are supplied with either current or voltage measurement channels to the customer's specification.

Current circuits use ferrite rings with an 8 mm internal diameter. Passing the current-circuit conductor through the ferrite ring forms the measuring circuit without introducing additional resistance into the current circuit.

Voltage and binary circuits connect directly to the module terminals without intermediate terminal blocks.

AURA-AK provides connections and galvanic isolation for 64 binary channels. The transducer modules contain optocouplers with a 3000 V isolation rating and binary signal switching circuits. An isolated power supply on the backplane (concentrator) provides the 30 V sensing voltage for binary signals.

The binary signal must be provided by a volt-free contact or a semiconductor device with the required switching current and voltage ratings.

The binary input acquisition module draws 2–10 mA in the closed state with a circuit resistance of up to 500 Ω.

When semiconductor devices generate the binary signal, their residual current in the open state must not exceed 0.1 mA for reliable detection.

The standard disturbance recording duration is 8 s. It can be configured in software over a range of 1–3,600 s.
The pre-fault recording duration is 0.1 s and can be configured in software up to 180 s. COMTRADE recording must be disabled when increasing the pre-fault recording duration.

Available trigger settings:
  • when an input exceeds or falls below its threshold, on any analog channel;
  • activation or deactivation of any binary channel.

The maximum intrinsic absolute clock error of AURA-AK without time synchronization signals is 10 seconds per day.
AURA-AK becomes operational within 30 seconds.

AURA-AK provides binary outputs to indicate a recording trigger or device fault. Each output switches a semiconductor solid-state relay between its closed and open states.
AURA-AK requires a 12 V DC ±10% supply. No supply-ripple requirement is specified for DC operation. The power supply arrangement is selected during system design. With suitable AC/DC or DC/DC converters, the recorder can be powered from 220 V ±44 V or 127 V ±25.4 V AC at 50 Hz, or from 220 V ±44 V or 72–144 V DC. For AC supplies, permissible frequency deviations and harmonic content are specified in GOST 13109.

Sampling rate versus channel count
Number of analog channels Number of binary channels Samples per cycle (scanning rate, Hz)
4 8 20…768 (1000…38400)
8 16 20…384 (1000…19200)
16 32 20…192 (1000…9600)
32 64 20…96 (1000…4800)
Recorder specifications
  • ADC resolution 12 bits
  • Triggers: any analog or binary channel, calculated U2(I2) and 3U0(3I0)
  • Maximum disk usage during disturbance recording 300 KB/s
  • Binary alarm output specifications:
    • Switching voltage up to 400 V
    • Switching current up to 50 mA
  • Processor clock speed at least 800 MHz
  • RAM at least 1 GB
  • Storage at least 8 GB flash or an 80 GB hard drive
  • Communications: Ethernet at 10 Mbit/s or higher, remote modem access, Bluetooth, Wi-Fi
  • Disturbance file size, kB: Lfault = Nchannels * 2 * Fsample × Trecord / 1024, where
    • Nchannels – number of recorder channels
    • Fsample is the sampling rate, Hz
    • Trecord is the recording duration, s
  • Operating temperature range: +1 to +45 °C

AURA-AK power consumption does not exceed 45 W.
The mean time between failures of replaceable AURA-AK components is at least 125,000 hours.
The mean service life of AURA-AK is at least 25 years.

AURA-AK is classified as O4 under GOST 15150 for climatic resistance. The recorder meets the safety requirements of GOST 22261-94 and GOST R 50377-92, the electromagnetic compatibility requirements of GOST R 50839-95 and GOST R 51318.22, and specification TU 4252-020-12325925-2011.
The AURA-AK digital fault recorder is listed in the Russian State Register of Measuring Instruments, registration no. 72492-18.

Accuracy class:
AC current and voltage: 0.5
DC current and voltage — 0.5
phase displacement: 0.5
frequency — 0.05

Example designation of an AURA-07 hardware and software system
  • AURA-AK, TU 4252-001-12325925-2013.
When ordering AURA-AK, also specify:
  • list of system hardware;
  • the input signal types and ranges;
  • additional software configuration;
  • additional equipment configuration.
Transducer specifications:

AURA-AK supports physical quantity transducers with DC output signals, or instantaneous AC current outputs, in the ranges −5…0…5, 0…5, −20…0…20, 0…20, 4…20 and −40…0…40 mA, and 75 mV shunts. Each current-loop analog input has an input resistance of 20 ±5 Ω.

The maximum permissible errors, expressed as a percentage of the reference value, with the input transducers under operating conditions do not exceed:
  • DC current: ±0.5%;
  • DC voltage: ±0.5%;
  • RMS AC current ±0.35%;
  • RMS AC voltage ±0.35%.
Transducer measurement ranges
Designation Measurement range and unit
Voltage transducer
PN-4~ 80 V AC 120 V AC 160 V AC 240 V AC
PN-4-a 150 mV–400 V *
AC current transducer
PT-4-10 1 A 2 A 5 A 10 A
PT-4-200 20 A 40 A 100 A 200 A

* Measurement ranges are set to the customer's requirements

Weight: 3.2 kg.

AURA-AK overall and mounting dimensions
  1. Disturbance recording, generating an AURA-format file or files in both AURA and COMTRADE formats;
  2. automatic processing of disturbance files, including a text report with disturbance analysis and fault location, and a time-limited extract containing the signals that changed during the disturbance;
  3. recording binary state changes by creating files listing the binary channels that changed state during the day;
  4. normal-condition recording: measurement files for normal operating channels, sampled every 5–180 seconds and retained for seven days;
  5. emailing newly recorded files and diagnostic messages, including over a dial-up modem connection;
  6. transferring newly recorded files to specified locations on the Ethernet network;
  7. transferring newly recorded files over IEC 60870-5-104;
  8. a web server for access to data through Internet Explorer;
  9. automatic copying of disturbance files to a USB flash drive when one is detected;
  10. network access over a dial-up modem connection;
  11. time synchronization:
    • Network Time Protocol (NTP) client;
    • support for multiple time servers;
    • synchronization to satellite navigation signals;
  12. self-diagnostics with status indication and event logging, including input transducer diagnostics;
  13. in the IEC 61850 version, receipt of binary status information using IEC 61850 GOOSE.

Data storage and transfer

Disturbance files are stored on the recorder's drive, in the AWR and COMTRADE folders, until deleted.

Files can be deleted in the following ways.
  1. manually;
  2. automatically after a new recording, by deleting the oldest file when disk usage reaches 80%;
  3. On a large drive, the number of files can reach several thousand, making them harder to manage. The recorder allows a maximum file count to be set. When a new recording exceeds this limit, the oldest excess file is deleted automatically.
At the recorder installation site, data can be retrieved in the following ways.
  1. By copying files from the recorder over Ethernet through Windows Network. Recorder access must be configured at the share or user level;
  2. downloading files directly through the web interface while access to the recorder's shared resources is disabled. Internet Explorer is used for this method. The web interface home page is password-protected;
  3. copying to laptops, handheld computers and mobile phones over Bluetooth or Wi-Fi. This requires a wireless access point or an optional wireless adapter installed in the recorder;
  4. By copying files directly from the recorder to a USB flash drive. When a drive is inserted into the USB port, recent disturbance files that have not yet been copied are copied automatically, together with a transfer report.
The recorders support several ways of delivering disturbance data to remote clients:
  1. downloading files directly over Ethernet, including remote access through telephone modems;
  2. downloading files directly through the web interface;
  3. automatically emailing data to specified addresses through a mail server. The recorder can automatically establish a dial-up modem connection to a configured number;
  4. transmission of disturbance records as measured values using IEC 60870-5-104.

Measurements under normal operating conditions are available through IEC 60870-5-104 and an OPC server.

Waveform transmission using IEC 60870-5-104. Data is transmitted spontaneously as soon as the disturbance file is recorded. The analog deadband is 5%. IEC 60870-5-104 timestamps allow signal envelopes to be reconstructed, including phase-angle envelopes.

AURA-AK with its measuring transducers provides:
  • direct and indirect measurement, using known relationships, of electrical and non-electrical physical quantities during normal operation and fault conditions;
  • digital recording of electrical and non-electrical quantities during normal and fault operation of equipment;
  • online monitoring of equipment operating conditions;
  • data storage and transfer to higher-level systems.