The TransAURA recorder is a single integrated unit mounted in a carrying case. Its enclosure incorporates removable input measuring transducers and a binary input unit. TransAURA is supplied with input connection cables and current clamps. It can record disturbances and normal operating conditions or serve as a multichannel voltage, current and phase-angle meter.
Request a quoteThe TransAURA digital fault recorder is based on an industrial computer. Its circuit design, embedded software and functions are equivalent to those of AURA recorders.
The recorder is a single integrated unit mounted in a carrying case, with compartments for measurement cables and current clamps. Its enclosure incorporates removable input measuring transducers and a binary input unit. Input connection cables and current clamps are included.
The recorder is a single integrated unit mounted in a carrying case, with compartments for measurement cables and current clamps. Its enclosure incorporates removable input measuring transducers and a binary input unit. Input connection cables and current clamps are included.
TransAURA includes an industrial-computer-based main unit, system software, measuring transducers and communication equipment.
TransAURA variants offer different combinations of current and voltage transducers, with a maximum of 16 transducers.
The standard TransAURA configuration includes:Application software for PC workstations running Windows is included.
The TransAURA recording unit has an industrial, vibration-resistant aluminum extrusion enclosure and a single-board computer with fanless cooling.
The front panel contains:The operating system is based on the Linux kernel.
The voltage input transducers accept both AC and DC signals. Each analog voltage channel has an input impedance of no more than 20 kΩ. Current is measured using current clamps connected to the current transducer inputs.
The N-0.6 transducer can measure current through a shunt.
The recorder accepts two-state binary signals from volt-free contacts or solid-state switching devices. It connects and galvanically isolates 32 binary channels.
The TransAURA digital fault recorder is listed in the Russian State Register of Measuring Instruments, registration no. 72492-18.
Transducer specifications:The binary input circuit draws 2–10 mA with a line resistance of up to 500 Ω. Isolation voltage is 3,000 V. Binary channels are powered from a galvanically isolated 24 V supply.
| Type | Ranges (software-selectable) | |||
|---|---|---|---|---|
| T-2000 current transducer | 1 A AC | 2 A AC | 5 A AC | 10 A AC |
| 10 A AC | 20 A AC | 50 A AC | 100 A AC | |
| 20 A AC | 40 A AC | 100 A AC | 200 A AC | |
| 100 A AC | 200 A AC | 500 A AC | 1000 A AC | |
| 200 A AC | 400 A AC | 1000 A AC | 2000 A AC | |
| N-0.6 DC and AC voltage transducer | 0.105 V DC | 0.21 V DC | 0.42 V DC | 0.84 V DC |
| 0.075 V AC | 0.15 V AC | 0.3 V AC | 0.6 V AC | |
| N-120 AC/DC voltage transducer | 21 V DC | 42 V DC | 84 V DC | 168 V DC |
| 15 V AC | 30 V AC | 60 V AC | 120 V AC | |
| N-250 DC and AC voltage transducer | 43.75 V DC | 87.5 V DC | 175 V DC | 350 V DC |
| 31.25 V AC | 62.5 V AC | 125 V AC | 250 V AC | |
| NP-120 AC voltage transducer | 15 V AC | 30 V AC | 60 V AC | 120 V AC |
Weight: 16 kg.
Number of recorders __________
Input transducer kit for each recorder
| No. | Transducer type | Quantity |
|---|---|---|
Order prepared by _____________________________________________
Signature / Printed name
(Date)
| No. | Transducer type | Quantity |
|---|---|---|
| 1 | N-0.6 | 4 |
| 2 | N-120 | 4 |
| 3 | T-2000 (100 A) with current clamps | 4 |
| 4 | T-2000 (200 A) + current clamps | 4 |