Frequently asked questions


General questions

This means that the database is configured incorrectly. Connect a monitor and keyboard, back up the database to a USB drive, then load a correct database from the drive, for example the database supplied with the recorder.

Option 1: Connect to the recorder using AuraServ, then save the file using “File → Save”.

Option 2: Extract from a disturbance recording file in AURA2000 using the command “File → Extract database”.

Option 3 Connect to the network drive, if access is enabled, and download the file "*.dta".

The factory-set address is listed in the factory test report. The program AuraServ can find recorders on the network. If none are detected, disable the antivirus and firewall. Discovery works even when the recorder's address is on another subnet. To establish a connection, however, assign the network adapter an address on the same subnet.

For example, if the recorder has address 169.254.0.22 and subnet mask 255.255.0.0, assign the laptop an address 169.254.x.x, where x is from 1 to 254, avoiding the recorder's address ending in 0.22. The address portions corresponding to 255 in the mask must match, while the host address must be different.

After switching on the power, wait for a short beep and immediately press DEL or F2 on the keyboard.

AuraServ:
  • TCP server (also the web server) and UDP server/client: 8090.
AuraPort:
  • TCP server, including the web interface, and UDP server/client: 8090;
  • IEC 60870-5-104 uses ports 2404, 2405 and 2406.
    • 2404 for normal operating measurements;
    • 2405 for disturbance file transfer;
    • 2406 for normal operating measurements and disturbance files.
AuraMaster:
  • 8090 and 8091.
TeleAura:
  • To communicate with AuraMaster – 8091.

PostAwr software

In the folder containing the file PostAwr.exe. The application creates it at startup.

AuraPort

In AuraPort go to “Settings”, select the checkbox “Use Latin characters in disturbance file names”.

In AuraPort go to “Settings → Precise time”, select the checkbox “PPS synchronization”and select the channel. Time synchronization will then operate, and this channel will be excluded from BOX files.

Aura2000

In primary quantities.

In primary quantities.

All measurements use the fundamental harmonic.

Text report generation is independent of the measurement display modes selected in the viewer.

  1. The program Aura2000 must be run as administrator. Right-click its icon and select Run as administrator;
  2. “Settings → Directories” must point to the location of the files "*.rx";
  3. the recorder number in the line description file must match the recorder that produced the disturbance file.

AuraServ software

Channels selected in the database for normal-operation measurements are included in the live measurements sent to higher-level systems over the AURA internal protocol or IEC 60870-5-104. To enable IEC 60870-5-104, open AuraPort settings and select the checkbox “IEC 60870-5-104 protocol”. To view the channel order in a text editor, locate the "C:\AURA\" folder on the recorder and open "*.s104", where "*" is the recorder number. In the service program, normal-operation measurements are displayed on the tab “Status → Normal operation”.

Yes, “A” is an AC analog channel, “AC” means an analog DC channel.

The settings of the checkboxes “normal” / “disturbance” in the database. The checkbox “disturbance” is reserved for future functionality and, in version AuraPort 6.1.0.25 has no effect. The checkbox “Normal” affects the calculation and transmission of normal operating measurements.

  1. in AuraServ establish a connection;
  2. “Files → Replace *.dta file”.

Set the “Site” field to “TransAURA”, save the database and close AuraServ, start AuraServ again and open the database file. You will then see the “TransAURA” button in the “Database” window.

Yes, in secondary quantities.

They specify the signal type applied to the PT/PN analog transducer input.

It sets the reset ratio: the reset value divided by the operating value. This prevents trigger chatter when the measured value is close to the threshold.

The trigger element picks up at 1.1 A and resets at 0.5 A. Until it resets, the indicator remains lit and cannot be cleared manually. Once the value falls below 0.5 A, the latched indication can be cleared manually. Falling to 1.1 A has no effect, as that is the pickup threshold. The recorder triggers only once when the threshold is exceeded, regardless of how long the triggering condition lasts.

Suppose the pickup and reset thresholds are both set to 1.1 A. If the measured value fluctuates around this threshold, for example between 1.11 and 1.099 A, a new trigger occurs every time it crosses the threshold. A reset ratio prevents this repeated triggering. A 20 ms trigger delay also prevents short interference pulses from triggering the recorder.

If the recorder is retriggered during a disturbance recording—that is, the threshold is exceeded, the signal returns to its original state, and the threshold is exceeded again—the recording timer restarts. For example, with an 8 s recording duration, a retrigger at the fourth second produces a total recording duration of 12 s.

Typically, the following triggers are set for each busbar system:
  • for 3U0 — above normal,
  • for U2 — above normal,
  • for a balanced voltage reduction — below normal.

To detect a symmetrical voltage drop, a threshold on one phase is sufficient. This is enough to trigger the recorder for all fault conditions.

For major 500 kV and 330 kV transmission lines, the following additional thresholds are set:
  • on 3I0 — above normal,
  • on I2 — above normal,
  • on a symmetrical current increase, also using one phase.

In ADC counts.

Check the messages under “Status → Messages”. If it contains the message “Interface unit not detected. Recorder started in emulation mode!”, either you have connected to the wrong recorder, for example to your own laptop running Auraport, or the interface unit is faulty.

The phase angles are calculated by AuraPort. The first analog channel with a signal level above 0.1% of the ADC full-scale value is used as the reference.