SPT transducers linearly convert AC overload current into a standardized AC current signal transmitted over a current loop up to 1,000 m long.
Request a quoteSPT transducers linearly convert AC overload current under fault conditions into a standardized AC signal measured through a current loop.
The transducer needs no external power supply, can be installed up to 1,000 m from the recorder, and connects to it using a twisted pair.
The transducers are housed in plug-in plastic enclosures. The cover is secured to the connector section with four screws and has two latches that lock the transducer into its mating connector. The input connector is similar to a conventional BI-6 test block. It shorts the current circuits when the transducer is withdrawn and permits current-injection testing and insulation testing of incoming cables. Guide ribs between connector contacts prevent short circuits if the transducer is accidentally tilted during insertion. The mating connector has M4 screw terminals for the input and output circuits.
automated measurement and control systems and digital fault recorders.
SPT-100/20-4 | | | |_____ number of measurement channels | | |_______ rated output current, mA | |___________ rated input current, A |_______________ device type
| Current, A | Number of overloads | Duration of each overload, s | Interval between overloads, s |
|---|---|---|---|
| 10 | continuous | ||
| 35 | 2 | 15 | 2,5 |
| 50 | 5 | 3 | 60 |
| 100 | 2 | 0,5 | 2.5 hours |
| 200 | 1 | 0,5 | 0.5 hours |
Weight: 0.8 kg.
Weight: 8.4 kg.