BKD-485

BKD-485

16-channel binary input module

  • No built-in line termination resistor
  • IEC 60870-5-101
  • RS-485

The BKD-485 16-channel binary input module with LED indication transmits status information over RS-485 using IEC 60870-5-101. It has no built-in line termination resistor.

Request a quote

LEDs indicate the current states relevant to module operation.

The module has no built-in 120 Ω line termination resistor.

Applications

The BKD-485 16-channel binary input module with LED indication transmits status indications over RS-485 using IEC 60870-5-101.

BKD-485
BKD-485 16-channel binary input module
Indicator functions
  • each status input terminal has an LED showing its state, green for open and red for closed;
  • the RX LED indicates valid data reception on the interface;
  • the “TX” LED indicates data transmission over the interface;
  • the Status LED flashes at 1 Hz to indicate that the module is operating;
  • The Power LED indicates that the module is powered. On modules with a built-in power supply, it indicates that voltage is applied to the terminals and current is flowing. Otherwise, the status contacts are not scanned and their reported states are invalid.
Transducer terminal assignments
Terminal numbers Function
1 - 16 Input for monitored status contacts
17, 18 Status input common conductor
19 RS-485 interface GND conductor
20 RS-485 conductor B
21 RS-485 interface wire A
34 Supply positive
35 Ground
36 Supply negative
Other Not used
Module operating conditions
Parameter Value
Ambient temperature, °C noncondensing −20 to +55
relative
humidity of 30–50%
+15 to +55
Atmospheric pressure, kPa 84–106
Supply voltage, V 18–36

Module operation is not guaranteed if storage, operating or transport conditions fall outside the requirements in the table.

Module connections

Connect the module according to the terminal assignments and observe the power supply polarity. Keep the RS-485 communication cable as short as possible. Fit termination resistors matching the twisted pair's characteristic impedance at the far ends of the cable to prevent interference from reflected signals.

Weight: 0.5 kg.

BKD-485 overall and mounting dimensions
  1. monitors up to 16 status inputs;
  2. stores status changes and their timestamps in the archive;
  3. monitors the current state of status contacts;
  4. allows time to be set over the protocol;
  5. software adjustment of baud rate and station address, status input checks and log-file generation.