TU-0201D

TU-0201D

remote control unit

  • Power consumption: no more than 3 VA
  • volt-free contact
  • RS-485

Remote control units are used in automated control and SCADA systems in the power sector and other industries. They operate output contacts in response to commands received over RS-485 and transmit binary signals from volt-free contacts.

Request a quote

TU-0201D remote control units switch their output contacts in response to commands received over RS-485 and transmit binary status signals from volt-free contacts.

Applications

automated control and SCADA systems in electric power facilities and other industries.

TU-0201D
TU-0201D remote control unit
  • Supply voltage: 90–260 V AC or 120–370 V DC
  • Power consumption from the supply circuit no greater than 3 VA
  • Switching voltage 0–240 V AC or 0–300 V DC
  • Switching current: 0–100 mA
  • Output pulse duration: 2 s, configurable to the customer’s requirements
  • Minimum interval between commands 0.4 s, adjustable to the customer's requirements
  • Number of volt-free contact inputs: 2
  • Volt-free contact interrogation voltage: 24–36 V
  • Maximum external circuit resistance of volt-free contact inputs in the closed state: 3 kΩ
  • External circuit resistance for volt-free contacts in the open state at least 100 kΩ
  • Closed-circuit current: 5–10 mA
  • RS-485 communication rates: 600, 1,200, 9,600, 19,200, 57,600 and 115,200 baud

Weight 0.3 kg.

TU-0201D overall and mounting dimensions