AURA-61850

AURA-08-D

Digital Fault Recorder (DFR)

The AURA-08-D recorder is designed for digital substations with an IEC 61850 process bus. It stores power-system disturbance waveforms on its own drive and subsequently transfers them to higher-level systems.

Request a quote

The AURA-08-D digital fault recorder stores power-system disturbance waveforms on its own drive and subsequently transfers them to higher-level systems. The recorder forms part of the AURA-07 hardware and software systems.

AURA-08-D receives digitized instantaneous analog measurements and binary signal states. It processes these values mathematically, for example using a Fourier transform for analog signals and a debounce filter for binary signals, then compares the results against user-defined settings to detect the onset of a power-system disturbance. When a trigger condition is met, it records a COMTRADE disturbance file containing all recorded quantities over a configured interval before and after the trigger. The recorded files are made available for event analysis. The recorder also performs an initial automatic event analysis and provides its results to the user.

The recorder also provides related functions, including calculating and transmitting RMS measurements for diagnostics, SCADA and process control, and recording network traffic during a disturbance for subsequent analysis.

Design

The recorder is built on a Vecow hardware platform; other hardware platforms can also be used.

Applications

digital substations with an IEC 61850 process bus.

Interoperability has been tested with devices from the following manufacturers.
  • AST
  • Bresler
  • Mechatronika
  • Prosoft
  • Relematika
  • Uralenergoservice
  • ChEAZ
  • EKRA
  • Energoservice
  • ABB
  • GE
  • Siemens
  • SVEY’s own analog and binary signal transducers
Waveform recording parameters
Parameter Value
Maximum trigger response time, ms 10
Pre-fault recording duration, s 0…60
Continuous disturbance recording duration, s 0…3600+
Post-fault recording duration, s 0…3600+
Sustained-trigger blocking Yes
Automatic disabling and re-enabling of triggers that remain continuously active Yes
Total duration of waveform records stored simultaneously in the recorder’s nonvolatile memory, per 100 GiB of allocated storage, h Calculated using the formula below
- with 256 analog channels, 1,024 binary channels, 1,000 Hz sampling and BINARY format 40
– with 256 analog channels, 4096 binary channels, 2400 Hz sampling and FLOAT32 format 10
A simplified formula for calculating the maximum total duration of stored disturbance records:
  • T = 3 * 107 / (A * N + D / 8 + 8) / F, where:
  • T is the total duration of disturbance records stored in 100 GiB of disk space
  • A — number of analog channels
  • N is the size of an analog value (2 for BINARY format, 4 for FLOAT32 format)
  • D is the number of binary channels
  • F is the COMTRADE file sampling rate

Enabling network traffic recording consumes additional disk space in proportion to the actual volume of recorded traffic, which may reduce the total duration of waveform records that can be stored.

The recorder log can hold up to 40 MiB. It consists of text files: up to nine completed 4 MiB files and one current file of up to 4 MiB. The log is accessible through the web interface and is copied automatically to a connected USB flash drive. When the log reaches its capacity, the oldest file is deleted.

  • Absolute frequency measurement error no greater than ±0.05 Hz
  • Up to 6 network interfaces
  • Weight: 3.8 kg.
AURA-08-D overall and mounting dimensions
  • Available with mounting brackets for a 19-inch rack
  • Weight: 6.1 kg.
Overall and mounting dimensions of the 19-inch rack mount

Some specifications may vary with the hardware platform used.

  1. Acquisition of AC and DC voltage and current signals by sampling instantaneous values and converting them into a digital sequence quantized in amplitude and time at the configured sampling rate;
  2. calculating RMS values, mean values and symmetrical components of analog signals by digitally processing the recorded samples;
  3. determining the fundamental frequency of the recorded AC current and voltage signals;
  4. recording binary signal states;
  5. saving recorded values and their associated attributes, including timestamps, channel names, transformer ratios and sampling rate, in IEEE Std C37.111 COMTRADE 2013 format;
  6. self-diagnostics with status indication and event logging;
  7. providing secure remote access to recorder data.

The recorder can also capture network traffic while recording a waveform. Captured traffic is saved in a *.pcap file and can be viewed and analyzed using suitable software, such as Wireshark.

The recorder software provides the following functions specified in STO 34.01-4.1-002-2017:
  • user authentication
  • user access rights and permissions management
  • configuration and trigger setting adjustment
  • continuous device health monitoring, with visual and binary fault indications
  • retrieval and copying of disturbance records to an external device
  • replacing the oldest disturbance data with new recordings
  • an event log in nonvolatile memory, protected from user editing, with new events replacing the oldest entries
  • automatic generation of a text report for each disturbance event